Brands
24DC, 5 AMP, POWER CONDITIONER
Overview
interVOLTS SPCi Power Conditioners Isolated Mini are condensed versions of the tried and proven Maxi Series range packed with all the same features and benefits.
Diagnostics
Unique to interVOLT, is the self diagnosing electronics. This design provides valuable feedback to installers and operators alike. An LED displays the system status and will indicate standby power, low input voltage, over temperature, overload and output short circuit.
Protection
interVOLT converters feature a range of devices designed to protect the electronics from various connection and application problems. The units are protected against short circuit, overloading and excessive temperature. An internal fuse protects the electronics in the event of component failure.
Performance
A key feature of the interVOLT mini series range is performance. Designed to operate in high ambient temperatures under constant load, the mini series delivers every time. Precise voltage regulation, superior noise filtering and excellent efficiency round off the performance package.
Conformity
interVOLT converters comply with Australian and European standards for electro-magnetic compatibility (EMC), displaying both the ‘C’ Tick and ‘CE’ marks. These approvals are supported by independent examination from a certified testing house. Our Declaration of Conformity is available upon request.
Isolation
A key feature of the new interVOLT SVCi mini series range is the input to output isolation. Galvanic isolation ensures there is no physical connectivity between the input and output terminals providing many benefits including elimination of line interference, greater protection, better regulation and improved performance.
Model | SPCi242405 |
Continuous Load Rating @ 30°C |
5 Amps @ 27.2VDC |
Peak Load Rating @ 30°C | 7 Amps @ 27.2VDC |
Length Overall | 170mm (6.690”) |
Width Overall | 80mm (3.150”) |
Height Overall | 40mm (1.575”) |
Weight | 418 grams (14.75 oz) |
Input Voltage Range | 17 – 33VDC |
Output Voltage – Low Setting | 25.0 VDC nominal |
Output Voltage – High Setting | 27.2 VDC nominal |
Standby Current Draw | <20mA |
Power Conversion Efficiency @ 30°C |
Typically 93% |
Output Ripple | Less than 20mV Peak to Peak |
Operating Temperature | -25°C to + 45°C |
Operating Humidity | Ideally less than 90% |
Enclosure Material | Marine grade aluminium dye anodised |
End Cap Material | Injection moulded electrical grade ABS/PC plastic |
Terminal Cover Material | Extruded temperature resistant ABS |
Diagnostic Indicator | Tri-colour LED – monitoring input voltage, overload, short circuit and temperature. |
Transient Voltage Protection | Filtering – Purpose designed circuit |
Overload/Short Circuit Protection | Shutdown – Current sensing circuit (automatic reset) |
Input Under Voltage Protection | Shutdown – Voltage sensing circuit (automatic reset) |
Over Temperature Protection | Shutdown – Temperature sensing circuit (automatic reset) |
Output Over Voltage Protection | Internal Fuse – Zener crowbar circuit (not user serviceable) |
Input Reverse Polarity Protection | Internal Fuse – Diode bypass circuit (not user serviceable) |
Termination | Power – 6-32 UNC H/D screw terminal. Auxiliary – Euro terminal block |
Conformity | EMC – Australian AS/NZS CISPR 11. European EN55011.International CISPR 11 and IEC61204-3. |
Certification | EMC – Australian C Tick mark and European CE mark |